The current Openpath Jira and Confluence instances will be migrated to the MSI On-Premise solution from August 9th-11th, the current platform will be set to read-only and all future usage will be in the Avigilon Instance. Please ensure access to MSI Jira & MSI Confluence, both are accessible through OKTA. For additional information and details please refer to the Atlassian migration page

How to configure End-of-Line (EOL) supervision

The Single Door Controller, 4-Port, and 8-Port Board inputs have support for user-installed single or double 1k ohm termination. This lets you monitor cut or shorted lines and create alerts and rules in Alta Access. The input settings in Alta Access must match the physical wiring configurations.

EOL configurations and settings

To configure EOL in Avigilon Alta Access:

  1. Go to https://control.openpath.com/login and log in. To access the European Alta Access, please go to https://control.eu.openpath.com/login.

  2. Go to Devices > ACUs, then click on the ACU to edit.

  3. Click on the Ports tab.

  4. Click Cable next to the port with EOL configured.

  5. Select the appropriate End of Line Supervision setting from the dropdown, then click Save.

Related content

Operating current and power rating for all Avigilon Alta devices
Operating current and power rating for all Avigilon Alta devices
Read with this
How to create ACUs in Avigilon Alta Access
How to create ACUs in Avigilon Alta Access
More like this
How to set up the Single Door Controller
How to set up the Single Door Controller
More like this
How to set up an elevator in the Avigilon Alta Access
How to set up an elevator in the Avigilon Alta Access
More like this
Avigilon Alta Access app
Avigilon Alta Access app
More like this
Changing I/O types on 4 port and 8 port boards
Changing I/O types on 4 port and 8 port boards
More like this