The current Openpath Jira and Confluence instances will be migrated to the MSI On-Premise solution from August 9th-11th, the current platform will be set to read-only and all future usage will be in the Avigilon Instance. Please ensure access to MSI Jira & MSI Confluence, both are accessible through OKTA. For additional information and details please refer to the Atlassian migration page

Skip to end of metadata
Go to start of metadata

You are viewing an old version of this page. View the current version.

Compare with Current View Page History

« Previous Version 11 Next »

Nedap uPASS Reach readers use UHF RFID technology and are often used for long-range vehicle identification in parking garages.

Note: This reader requires external power. Current consumption: 1A @ 12VDC or 500mA @ 24VDC. For more information, refer to the uPASS Reach user guide.

Integrating uPASS Reach readers with Core Series hardware

Wiring uPASS Reach reader with Core Series hardware

Nedapp uPASS Reach

Openpath Core Series hardware

OUT2 (D0)

AUX1 (D0)

OUT3 (D1)

AUX2 (D1)

GND

GND

Integrating uPASS Reach readers with first-generation hardware

Wiring uPASS Reach reader with first gen hardware

Nedapp uPASS Reach

Openpath first gen hardware

OUT2 (D0)

D0

OUT3 (D1)

D1

GND

GND

Integrating uPASS Reach readers with Single Door Controller

Wiring uPASS Reach reader with Single Door Controller (SDC)

Nedapp uPASS Reach

Openpath SDC

OUT2 (D0)

D0

OUT3 (D1)

D1

GND

GND

Setting up uPASS Reach reader in the Control Center

To configure Wiegand inputs on Core Series hardware:

  1. Go to https://control.openpath.com/login and log in. To access the European Control Center, please go to https://control.eu.openpath.com/login.

  2. Go to Devices > ACUs, then click on the ACU to edit it

  3. Click on the Ports tab

  4. Click Port next to the first input of the I/O pair with the uPASS Reach reader configured

  5. Select Wiegand Device from the Input Type dropdown, then click Save

This will label the subsequent input as Wiegand Device (Extended) and disable it from editing. Inputs cannot be changed if they are already assigned to an entry.

Input settings in the Control Center

Once the Wiegand Device is configured on the ACU, it can be assigned to an entry. 

Assigning a Wiegand Device to an entry

For more information on creating Entries, refer to the Openpath User Guide.

To add a uPASS Reach reader to an entry:

  1. Go to https://control.openpath.com/login and log in. To access the European Control Center, please go to https://control.eu.openpath.com/login.

  2. Go to Sites > Entries and click on an existing entry to edit or click the plus(+) on the top right to Create an Entry

  3. Scroll down to Wiegand Device

  4. From the Port dropdown, select the port for the uPASS Reach reader to which this entry is wired

  5. From the Mode dropdown, select Input

  6. Click Save