Rule 1 - Door A in High State triggers Lockdown Plan associated with Door A and Door B
Rule 2 - Door A in Low State reverts Lockdown Plan associated with Door A and Door B
Rule 3 - Door B in High State triggers Lockdown Plan associated with Door A and Door B
Rule 4 - Door B in Low State reverts Lockdown Plan associated with Door A and Door B
To create Rule 1:
Go to Configurations > Rule Engine
Click Create Rule
Enter a name and description for the rule
In the Trigger section:
From the Type dropdown select Input
From the Event dropdown select Generic Input State Changed
In the Conditions section:
Click Add Condition
From the Type dropdown, select Input State
In the State to Match dropdown select high
Click Add Condition again
From the Type dropdown, select ACU Port Filter
From the ACU To Match dropdown, select the ACU with Door A
From the ACU Port To Match dropdown, select Door A's Generic Input
In the Actions section:
From the Type dropdown select Lockdown
From the Lockdown Plan dropdown, select the plan you created for Door A and Door B
From the Lockdown Action dropdown, select Trigger Lockdown
Click SaveClick Save
Your rule should look like the following:
Markdown |
---|
![mantrap rule step one](https://info.openpath.com/hubfs/images/kustomer-articles/mantrap-rule1.png) |
Markdown |
---|
![mantrap rule step 2](https://info.openpath.com/hubfs/images/kustomer-articles/mantrap-rule2.png) |
Markdown |
---|
![mantrap rule part 3](https://info.openpath.com/hubfs/images/kustomer-articles/mantrap-rule3.png) |
To create Rule 2, repeat the steps for Rule 1 but change the following:
In the State to Match dropdown select low
From the Lockdown Action dropdown, select Revert Lockdown
To create Rule 3, repeat the steps for Rule 1 but change the following:
From the ACU To Match dropdown, select the ACU with Door B
From the ACU Port To Match dropdown, select Door B's Generic Input
To create Rule 4, repeat the steps for Rule 1 but change the following:
In the State to Match dropdown select low
From the ACU To Match dropdown, select the ACU with Door B
From the ACU Port To Match dropdown, select Door B's Generic Input
From the Lockdown Action dropdown, select Revert Lockdown