The current Openpath Jira and Confluence instances will be migrated to the MSI On-Premise solution from August 9th-11th, the current platform will be set to read-only and all future usage will be in the Avigilon Instance. Please ensure access to MSI Jira & MSI Confluence, both are accessible through OKTA. For additional information and details please refer to the Atlassian migration page

Skip to end of metadata
Go to start of metadata

You are viewing an old version of this page. View the current version.

Compare with Current View Page History

« Previous Version 2 Next »

This wiring guide will explain the (4) wiring options supported by the 3rd party Power Supply used within our cabinet-based ACUs.

We do not offer any Fire Alarm Interface options for our Single Door Controllers (SDC) at this time.

FPV4 and FPV6 Power Supply Wiring

  1. The installer needs to confirm the trigger type being sent to the Openpath system from the FACP. The input from the FACP can be wired to accept a NO, NC, Open Collector, or Voltage input.

  2. Once the trigger type has been confirmed, please reference the wiring options below:

Important notes:

  • Fail-safe locksets MUST be used for operation. Fail-secure locksets do not toggle upon FAI activation.

  • Dip Switch 1 - FAI Selection: Off = Constant Output | On = Output switches on FAI. (see image below)

  • FAI LED #4 (Red) Indicates activation of the Fire Alarm Input. (see image below)

Expected Behavior:

Upon triggering the FAI, the Power Supply will disable all power outputs, shutting down all connected Openpath equipment.

Related Articles:

FPV4/6 Power Supply Installation Guide: https://www.lifesafetypower.com/docs/im_fpv-standard.pdf